[ Prev ]    Page:   1    2    3    4    5    6    7    8    [ Next ]

PDF version for print


 

Ramp and Skirting

 
 

Ramp: Steel ramp is available in heights 40, 50, 60, 76 mm and 100 mm. Length of ramp is minimum 12 times to finish floor height.

Skirting: Letter F-shape aluminum skirting is available in 6 standard heights 40, 50, 60, 76 and 100 mm.

Ramp Rail: Aluminum Ramp Rail to install horizontally at adjacent line of UniPanel and Ramp.

 

 

Specifications ---------------------------------------------
System: Netfloor CamassCrete series

 

1. Module Set

1.1

 

Module size: 600 mm x 600 mm (23.62" x 23.62")
=1 UniPanel + 1 Base Connector + 1 Central Cap + 4 Flank Caps.

1.2

 

System height:

1.2.1

 

CS1000A Super Low-Profile: 40 mm (1.57"), 50 mm (2.0"), 60 mm (2.36")

1.2.2

 

CS1000W Low-Profile: 76 mm (3") ~ 150 mm (6")

1.3

 

System weight: avg.36 kg / per sq. meter.

 

2. Main Components:

2.1

 

UniPanel (Main Panel)

2.1.1

 

Size: 510 × 510 mm (20.07" × 20.07")

2.1.2

 

Grooves: at four side of panel width 5 mm, length 410 mm, depth 8 mm from surface of panel.

2.1.3

 

Top plate and bottom plate of Panel: steel, corrosion protection with powder coating. Panel body in-filled with light weight cement

2.1.4

 

Pedestals: Galvanized steel, fixed at four corners. Assembled to system's required height.

2.2

 

Base Connector: steel, thickness 0.6 mm, corrosion protection by powder coating or electro-deposition.

2.3

 

Central Cap: steel, thickness 2.3 mm, corrosion protection by powder coating or electro-deposition.

2.4

 

Flank Cap: steel, thickness 2 mm corrosion protection by powder coating or electro-deposition, ribs reinforced at surface of the cap, 8 mm bent at flange to form a U-shape, bent flanges sealed by u-shape PVC trim to eliminate noise when contacting at grooves of the UniPanel.

2.5

 

Flank Cap with clamping device (optional): extra holding Flank Cap onto UniPanel (main panel).

 

3. Cable Trench Capacity

3.1

 

Inside width: 110 mm (4.33")

3.2

 

Cable Trench opening width: 90 mm (3.54")

3.3

 

Cable Trench clearance: system height minus 8 mm

3.4

 

Cable capacity under UniPanel (main panel): system height minus 28 mm.

 

4. Loading Property: UniPanel, in accordance with ASTM E-196

4.1

 

Concentration Load: (by 1 inch diameter indenter)
300 kg < 2.5 mm depression (660 LB < 2.5 mm depression)

4.2

 

Concentration Ultimate Load: (by 1 inch diameter indenter)
greater than 900 kg (> 1,980 LB)

4.3

 

Uniform Ultimate Load: greater than 50 psi

 

5. Flammability: Non-combustible. Meet BS476, part 4, ASTM E-84 class 1.

6. Surface Floor Covering: The system is not suitable to use as bare surface. Commercial rate carpet tile, or vinyl tile of more than 4.5 mm thick are standard surface flooring on top of the system.

7. Warranty: 5 years limited warranty.

In pursuing quality improvement, the manufacturer reserves the right to vary specifications without prior notice.

 

[ Prev ]    Page:   1    2    3    4    5    6    7    8    [ Next ]